TYCO Series ELO-231B 11.2K Standard
Response, Standard Coverage Upright
and Pendent Sprinklers (Ref. Figure 1)
are automatic sprinklers of the frangible
bulb type. They are standard response,
spray sprinklers that produce a hemispherical water distribution pattern
below the deflector.
The 11.2 K-factor, ELO-231B Sprinklers
were subjected to full-scale, high-piled
storage fire tests to qualify their use
in lieu of 5.6 or 8.0 K-factor standard
spray sprinklers for the protection of
high-piled storage.
- Approvals: UL, C-UL, FM & NYC
- Maximum Working Pressure: 175 psi (12,1 bar)
- Discharge Coefficient: K=11.2 GPM/psi½ (161.3 LPM/bar½).
- Pipe Thread Connection: 3/4 inch NPT (DN20)
- Finishes: NATURAL BRASS, LEAD COATED, WAX-OVER-LEAD COATED, CHROME PLATED
- Temperature Ratings:
+ 155 °F (68 °C) bulb liquid color red + 200 °F (93 °C) bulb liquid color green + 286 °F (141 °C) bulb liquid color blue- TY5151 was subjected to full-scale, high-piled storage fire tests to qualify their use in lieu of 5.6 or 8.0 K-factor standard spray sprinklers for the protection of high-piled storage.
- Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres.
- Intermediate level version of TY5151 for in-rack applications can be obtained by utilizing with the WSG-2 Guard & Shield